Page 64
Table 46. Analog Input Objects List
Object ID Data RangeUnitsObject Name
264 Most Recent Error 10 None 1 − 255
274 Space Carbon Dioxide Sensor (Effective) Parts−per−million 0 − 2000
275 Space Carbon Dioxide Sensor (Local) Parts−per−million 0 − 2000
276 Space Humidity (Effective) Percent 0 − 100
277 Space Humidity (Local) Percent 0 − 100
278 Dehumidification Set Point (Effective) Percent 0 − 100
279 Dehumidification Status None 0 − 2
281 Return Air Temperature Deg. F −8.7 – 164.4
282 Building Static Pressure Inches of water −0.5 − 0.5
283 Duct Static Pressure Inches of water 0 – 5.00
285 Exhaust Fan Status Percent 0 – 100
286 Supply Airflow Status cubic feet per minute 0 – 480 cfm/ton**
287 Blower Motor Speed RPM 0 – 1500
288 Blower Motor Torque Percent 0 – 100
289 Outdoor Airflow CFM 0–480 cfm/ton**
** Multiply the tonnage of the RTU with the value in cubic feet per minute/ton to derive the value in cubic feet minute units.