Page 75
18.4. Airflow Target Minimum - Maximum Settings
Parameter
Number
ENERGENCE A BOX WITH SMART
AIRFLOW (ADVANCE AIRFLOW)
(LCH/LGH)
CFM VALUES BY MODEL
NOTES
036 048 060
12 SMOKE DEFAULT CFM 1200 1600 2000
13 SUPPLY AIRFLOW HEAT TARGET 1200 1600 2000 For both gas & electric heating.
14 HIGH SPEED TARGET (COOLING HI) 1080 1440 1800
17 LOW SPEED TARGET (COOLING LOW) 780 1040 1300
< MAX SETTABLE VALUE = COOLING HIGH
CFM VALUE.
18 VENTILATION AIRFLOW TARGET (G) 450 600 750
< MAX SETTABLE VALUE =
MAXIMUM OF COOLING HIGH CFM OR
HEATING CFM
- COOLING HIGH MAXIMUM 1440 1920 2400 < MAX = 480 CFM/TON
- COOLING HIGH MINIMUM CFM 840 1120 1400 < MIN = 280 CFM/TON
- COOLING LOW MINIMUM CFM 660 880 1100 < MIN = 220 CFM/TON
- VENTILATION MINIMUM CFM 450 600 750 < MIN = 150 CFM/TON
-
STANDARD GAS HEAT (S, W)
MINIMUM CFM
970 970 970
-
MEDIUM GAS HEAT (M, Q, U, Y)
MINIMUM CFM
1120 1120 1120
HIGH GAS HEAT (H, T, X, Z) MIN CFM
Not
Applicable
1310 1310
ELECTRIC HEAT MINIMUM CFM 1080 1280 1600
For units: LCH036H_E / LCH048H_E /
LCH060H_E is published in Electric Heat In
stallation Instructions, Form # 50684701,
dated 9/1/2011.