EasyManuals Logo
Home>Lennox>Furnace>SIGNATURE SLP99DFV

Lennox SIGNATURE SLP99DFV User Manual

Lennox SIGNATURE SLP99DFV
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
Page 5
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be
installed in parallel with, or on the upstream side of, cool-
ing units to avoid condensation in the heating compart-
ment. With a parallel ow arrangement, a damper (or
other means to control the ow of air) must adequately
prevent chilled air from entering the furnace (FIGURE 3).
If the damper is manually operated, it must be equipped to
prevent operation of either the heating or the cooling unit,
unless it is in the full HEAT or COOL setting.
AIR HANDLER
GAS UNIT
Dampers
(open during cooling
operation only)
Dampers
(open during heating
operation only)
FURNACE INSTALLED PARALLEL
WITH COOLING COIL
FIGURE 3
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Elec-
tric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following ad-
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
NOTE - This furnace is designed for a minimum contin-
uous return air temperature of 60°F (16°C) or an inter-
mittent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air tem-
perature must not exceed 85°F (29°C) dry bulb. See “Duct
System” on page 9 for installing the optional discharge
air sensor used to measure temperature rise. Sensor is
shipped with the unit.
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of
the Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
CAUTION
Do not set thermostat below 60F (16C) in heating mode.
Setting below 60F (16C) reduces the number of heating
cycles. Damage to the unit may occur that is not covered
by the warranty.
The SLP99DFV furnace may be installed in alcoves, clos-
ets, attics, basements, garages, and utility rooms.
This furnace is not designed for installation in mobile
homes, recreational vehicles, or outdoors.
Never use an open ame to test for gas leaks. Check all
connections using a commercially available soap solution
made specically for leak detection.
Use of Furnace as Construction Heater
Units may be used for heating of buildings or structures
under construction, if the following conditions are met to
ensure proper operation:
DO NOT USE THE UNIT FOR CONSTRUCTION HEAT
UNLESS ALL OF THE FOLLOWING CRITERIA ARE
MET:
Furnace must be in its nal location. The vent system
must be permanently installed per these installation in-
structions.
Furnace must be installed as a two pipe system and
one hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc-
tion.
A room thermostat must control the furnace. The use
of xed jumpers that will provide continuous heating is
prohibited.
The input rate and temperature rise must be set per the
furnace rating plate.
Supply and Return air ducts must be provided and
sealed to the furnace. Return air must be terminated
outside of the space where furnace is installed.
Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
MERV 11 or greater air lters must be installed in the
system and must be regularly inspected and maintained
(e.g., regular static checks and replaced at end of life)
during construction.
Blower and vestibule access panels must be in place on
the furnace at all times.
The furnace heat exchanger, components, duct system,
and evaporator coils must be thoroughly cleaned follow-
ing nal construction clean−up.
Air lters must be replaced upon construction comple-
tion.
All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be veried
in accordance with these installation instructions.
EQUIPMENT MAY EXPERIENCE PREMATURE COM-
PONENT FAILURE AS A RESULT OF FAILURE TO FOL-
LOW THE ABOVE INSTALLATION INSTRUCTIONS.
FAILURE TO FOLLOW THE ABOVE INSTALLATION IN-
STRUCTIONS VOIDS THE MANUFACTURER’S EQUIP-
MENT LIMITED WARRANTY. LENNOX DISCLAIMS
ALL LIABILITY IN CONNECTION WITH INSTALLER’S
FAILURE TO FOLLOW THE ABOVE INSTALLATION IN-
STRUCTIONS.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox SIGNATURE SLP99DFV and is the answer not in the manual?

Lennox SIGNATURE SLP99DFV Specifications

General IconGeneral
BrandLennox
ModelSIGNATURE SLP99DFV
CategoryFurnace
LanguageEnglish

Related product manuals