Parameter
code
Parameter name
Parameter
range
Default
value
Note
P34
Clock Timer
repetition is valid
00: once
01: repeat everyday
00
Available only when timer is
set to clock timer.
P37
Cooling setting
temperature
under auto mode
17°C~30°C(63°F~86°
F)
25°C
(77°F)
When the temperature unit
is°C, cooling setting
temperature minus heating
setting temperature≥1°C.
When the temperature unit
is°F, cooling setting
temperature minus heating
setting temperature≥2°F.
P38
Heating setting
temperature
under auto mode
16°C~29°C(61°F~84°
F)
20°C
(68°F)
P43
Set priority
operation
00: normal operation
01: priority operation
00
When power supply is
insufficient, the indoor units
which are set to priority
operation can operate, while
other indoor units are forced
to be turned off.
P46
Clear Filter Clean
accumulated time
00: do not clear
01: clear
00
--
P49
Opening angle of
indoor unit
air-return plate*
01: angle 1(25°)
02: angle 2(30°)
03: angle 3(35°)
01
Only applicable to units with
air-return plate