19
ELECTRIC HEAT DATA 018-036
VVCA018H4
Description
Input
Blower Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Blower Speed
Low Medium High
Volt kW
1
Btuh
5 kW V8EH0050P-1P (13P59) 208 3.8 12,800 3.0 26.8 30 • • •
220 4.2 14,300 3.0 27.8 30 • • •
230 4.6 15,700 3.0 28.8 30 • • •
240 5.0 17,100 3.0 29.8 30 • • •
7.5 kW V8EH0080P-1P (13P63) 208 5.6 19,200 3.0 37.8
4
40
5
- - - • •
220 6.3 21,500 3.0 39.8
4
40
5
- - - • •
230 6.9 23,500 3.0 41.8 45
5
- - - • •
240 7.5 25,600 3.0 42.8 45
5
- - - • •
VVCA024H4
Description
Input
Blower Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Blower Speed
Low Medium High
Volt kW
1
Btuh
5 kW V8EH0050P-1P (13P59) 208 3.8 12,800 3.0 26.8 30 • • •
220 4.2 14,300 3.0 27.8 30 • • •
230 4.6 15,700 3.0 28.8 30 • • •
240 5.0 17,100 3.0 29.8 30 • • •
7.5 kW V8EH0080P-1P (13P63) 208 5.6 19,200 3.0 37.8
4
40
5
- - - • •
220 6.3 21,500 3.0 39.8
4
40
5
- - - • •
230 6.9 23,500 3.0 41.8 45
5
- - - • •
240 7.5 25,600 3.0 42.8 45
5
- - - • •
10 kW V8EH0100P-1P (13P64) 208 7.5 25,600 3.0 48.8
4
50
5
- - - • •
220 8.4 28,700 3.0 51.8 60
5
- - - • •
230 9.2 31,400 3.0 53.8 60
5
- - - • •
240 10.0 34,100
3.0 55.8 60
5
- - - • •
VVCA030H4
Description
Input Blower Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Blower Speed
Volt kW
1
Btuh Low Medium High
5 kW V8EH0050P-1P (13P59) 208 3.8 12,800 3.0 26.8 30 • • •
220 4.2 14,300 3.0 27.8 30 • • •
230 4.6 15,700 3.0 28.8 30 • • •
240 5.0 17,100 3.0 29.8 30 • • •
7.5 kW V8EH0080P-1P (13P63) 208 5.6 19,200 3.0 37.8
4
40
5
- - - • •
220 6.3 21,500 3.0 39.8 45
5
- - - • •
230 6.9 23,500 3.0 41.8 45
5
- - - • •
240 7.5 25,600 3.0 42.8 45
5
- - - • •
10 kW V8EH0100P-1P (13P64) 208 7.5 25,600 3.0 48.8
4
50
5
- - - • •
220 8.4 28,700 3.0 51.8 60
5
- - - • •
230 9.2 31,400 3.0 53.8 60
5
- - - • •
240 10.0 34,100 3.0 55.8 60
5
- - - • •
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Bold text indicates that the circuit breaker on CB” circuit breaker models must be replaced with size noted. See Table on page <OV>.
5
Do not operate fan on low speed when V8EH Electric Heat Kit is used with VVCA air handler.