Page 3
XC21
Electrical Data
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XC21−024−230−04 25 15.7 10.3 52.0 1/3 700 820 2.8
XC21−024−230−05 30 18.9 13.5 58.3 1/4 475 550 2.0
XC21−024−230−06 30 18.9 13.5 58.3 1/4 475 550 2.0
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XC21−036−230−04 40 23.7 16.7 82.0 1/3 700 820 2.8
XC21−036−230−05 35 22.9 16.7 82.0 1/4 475 550 2.0
XC21−036−230−06 35 22.9 16.7 82.0 1/4 475 550 2.0
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XC21−048−230−04 50 29.3 21.2 96.0 1/3 700 820 2.8
XC21−048−230−05 45 28.5 21.2 96.0 1/4 600 675 2.0
XC21−048−230−06 45 28.5 21.2 96.0 1/4 600 675 2.0
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XC21−060−230−04 60 34.9 25.7 118.0 1/3 700 820 2.8
XC21−060−230−05 50 25.7 25.7 118.0 1/4 600 675 2.0
XC21−060−230−06 50 25.7 25.7 118.0 1/4 600 675 2.0
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.