CMVPFB01A 34
Advanced Features
7.1.4 Module Time-out Action
P404 - Module Time-out Action
Default: 3 Range: 0 - 3
Access: RW Type: Integer
This parameter controls the action to be taken in the event of a Module-to-Drive time out. The Time-out
period is fixed at 200 ms.
Table 32: Module Time-out Action
P404 Value Description
0 No Action
1 Stop (controlled by P111)
2 Quick Stop
3
Fault F.ntf
7.1.5 Module Firmware
P494 - Module Firmware
Default: N/A Range: 1.00 - 99.99
Access: RO Type: Integer
Displays the module firmware revision in the format of xx.yy, where: xx = Major version and yy = Minor
version
7.1.6 Module Internal Code
P495 - Module Internal Code
Default: 209-yy Range:
Access: RO Type: Integer
Displays the internal code revision in the format of xxx-yy. The display alternates between xxx- and -yy.
7.1.7 Missed Messages
P498 and P499 - Missed Messages
Default: N/A Range:
Access: RO Type: Integer
Table 33: Missed Messages
Parameter Function Description
P498 Missed Messages
Drive to Module
Displays the quantity of missed data messages being
transmitted from the drive to the option module
P499 Missed Messages
Module to Drive
Displays the quantity of missed data messages being
transmitted from the option module to the drive

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze AC Tech SMVector PROFIBUS-DP and is the answer not in the manual?

Lenze AC Tech SMVector PROFIBUS-DP Specifications

General IconGeneral
BrandLenze AC Tech
ModelSMVector PROFIBUS-DP
CategoryControl Unit
LanguageEnglish

Related product manuals