2
Lenze
2-22
8200 motec/starttec en 12/03
Standard controllers
starttec – Technical data
Conformity CE Low Voltage Directive (73/23/EEC)
Approvals UL508 Industrial Control Equipment (File No. E221123)
Standards DIN EN 60947-4-2 Semiconductor motor controllers
and starters for alternating voltage
Vibrational stability Accelerational stability up to 4 g (Germanischer Lloyd, general conditions)
Climatic conditions Class 3K3 to EN 50178 (without condensation, average relative humidity 85%)
Pollution degree VDE 0110 Part 2, pollution degree 2
Packaging (DIN 4180) Dust packaging
Permissible temperature ranges
Transport -25°C ... +70°C
Storage -25°C ... +60°C
Operation -25°C ... +60°C for motor mounting
-25°C ... +40°C for wall mounting
Permissible installation height 0 ... 4000 m above The rated output current should be derated by 5%/1000 m
sea level above 1000 m above sea level.
Mounting positions All mounting positions and mounting orientations permitted
Mounting space
Above/below ≥100 mm
To the side >100 mm
Standards and operating conditions
EMC Complies with requirements to EN60947-4-2
Noise emission Complies with requirements to limiting class B to EN60947-4-2
Noise immunity Requirements to EN60947-4-2
Insulation strength Overvoltage category III to VDE 0110
Leakage current to PE < 3.5 mA
(to EN 50178)
Degree of protection IP65; NEMA4
Protective measures against Motor over temperature (input for PTC or thermal contact, I
2
t monitoring)
Total insulation of Mains isolation: Double/reinforced insulation to EN 50178
control circuits
Control method Generalised phase control
General electrical data