9
L
Keypad RemedyCauseErrorPC
1)
c
cc
ce
ee
e3
33
3
*
64 Communication error to
CAN-IN1 w ith e vent or
time control
CAN-IN1 object receives faulty data or
communication is interrupted
z
Plug-in connection - bus module
Ù
Check FIF
z
Check transmitter
z
Increase monitoring time under C0357/3
if necessary
c
cc
ce
ee
e4
44
4
*
65 BUS-OFF
(many c ommunication
faults occurred)
Controller has received too man y
incorrect telegrams via the system
bus and has been disconnected
z
Check w hether bus terminator available
z
Check screen contact of the cables
z
Check PE connection
z
Check bus load, if necessar y, reduce the
baud rate
c
cc
ce
ee
e5
55
5
*
66 CAN Time-Out
(configurable in C0126)
For remote parameter setting via
system bus (C0370):
Slave does not answer.
Communication monitoring time
exceeded.
z
Check system bus wiring
z
Check system bus configuration
For operation with application I/O:
Faulty parameter setting of parameter
set changeover
In all parameter sets the signal ”parameter
set c hangeover” (C0410/13, C0410/14)
must be combined with the same source
For operation with module in F IF:
Internal fault
Contact Lenze
c
cc
ce
ee
e6
66
6
*
67 Function module
system bus (CAN) on
FIF has set ”Warning”
or ”BUS-OFF”
(configurable in C0126)
CAN controller sets ”Warning” or ”BUS
OFF”
z
Check w hether bus terminator available
z
Check screen contact of the cables
z
Check PE connection
z
Check bus load, if necessar y, reduce the
baud rate
c
cc
ce
ee
e7
77
7
*
68 Communication fault
during remote
parameter s etting via
system bus (C0370)
(configurable in C0126)
Participant does respond or is not
available
z
Check w hether bus terminator available
z
Check screen contact of the cables
z
Check PE connection
z
Check bus load, if necessar y, reduce the
baud rate
For operation with application I/O:
Faulty parameter setting of parameter
set changeover
In all parameter sets the signal ”parameter
set c hangeover” (C0410/13, C0410/14)
must be combined with the same source
E
EE
EE
EE
Er
rr
r
*
91 External fault
(TRIP-SET)
A digital input assigned to the
TRIP-Set function has been activa ted.
Check external encoder
E
EE
Er
rr
rP
PP
P0
00
0
.
..
..
..
..
..
.
E
EE
Er
rr
rP
PP
P1
11
19
99
9
*
- Communication abort
between keypad and
basic device
Various Contact Lenze
F
FF
FA
AA
An
nn
n1
11
1
*
95
E82ZMV fan module
(only 8200 motec
3 ... 7,5 kW)
Fan module is defect Replace fan module
F
FF
FA
AA
An
nn
n1
11
1
-