EasyManuals Logo

Lenze 8200 vector Getting Started

Lenze 8200 vector
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
9
L
Keypad RemedyCauseErrorPC
1)
c
cc
ce
ee
e3
33
3
*
64 Communication error to
CAN-IN1 w ith e vent or
time control
CAN-IN1 object receives faulty data or
communication is interrupted
z
Plug-in connection - bus module
Ù
Check FIF
z
Check transmitter
z
Increase monitoring time under C0357/3
if necessary
c
cc
ce
ee
e4
44
4
*
65 BUS-OFF
(many c ommunication
faults occurred)
Controller has received too man y
incorrect telegrams via the system
bus and has been disconnected
z
Check w hether bus terminator available
z
Check screen contact of the cables
z
Check PE connection
z
Check bus load, if necessar y, reduce the
baud rate
c
cc
ce
ee
e5
55
5
*
66 CAN Time-Out
(configurable in C0126)
For remote parameter setting via
system bus (C0370):
Slave does not answer.
Communication monitoring time
exceeded.
z
Check system bus wiring
z
Check system bus configuration
For operation with application I/O:
Faulty parameter setting of parameter
set changeover
In all parameter sets the signal ”parameter
set c hangeover” (C0410/13, C0410/14)
must be combined with the same source
For operation with module in F IF:
Internal fault
Contact Lenze
c
cc
ce
ee
e6
66
6
*
67 Function module
system bus (CAN) on
FIF has set ”Warning”
or ”BUS-OFF”
(configurable in C0126)
CAN controller sets ”Warning” or ”BUS
OFF”
z
Check w hether bus terminator available
z
Check screen contact of the cables
z
Check PE connection
z
Check bus load, if necessar y, reduce the
baud rate
c
cc
ce
ee
e7
77
7
*
68 Communication fault
during remote
parameter s etting via
system bus (C0370)
(configurable in C0126)
Participant does respond or is not
available
z
Check w hether bus terminator available
z
Check screen contact of the cables
z
Check PE connection
z
Check bus load, if necessar y, reduce the
baud rate
For operation with application I/O:
Faulty parameter setting of parameter
set changeover
In all parameter sets the signal ”parameter
set c hangeover” (C0410/13, C0410/14)
must be combined with the same source
E
EE
EE
EE
Er
rr
r
*
91 External fault
(TRIP-SET)
A digital input assigned to the
TRIP-Set function has been activa ted.
Check external encoder
E
EE
Er
rr
rP
PP
P0
00
0
.
..
..
..
..
..
.
E
EE
Er
rr
rP
PP
P1
11
19
99
9
*
- Communication abort
between keypad and
basic device
Various Contact Lenze
F
FF
FA
AA
An
nn
n1
11
1
*
95
E82ZMV fan module
(only 8200 motec
3 ... 7,5 kW)
Fan module is defect Replace fan module
F
FF
FA
AA
An
nn
n1
11
1
-
3
.
.
.
7
,
5
k
W
)
TRIP or warning
configurable under
C0608
Fan module is not connected Connect fan module
Check wiring
H
HH
H0
00
05
55
5
*
105 Internal fault Contact Lenze

Other manuals for Lenze 8200 vector

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8200 vector and is the answer not in the manual?

Lenze 8200 vector Specifications

General IconGeneral
CategoryDC Drives
Series8200 vector
Enclosure RatingIP20
Control MethodVector control
CommunicationCANopen, DeviceNet, Profibus
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Humidity< 95 % non-condensing
Operating Temperature0 to +45 °C (derating above 40°C)

Related product manuals