Technical data
General data and operating conditions
2
42
MA 13.0001 DE-EN DE/EN 2.0
2 Technical data
2.1 General data and operating conditions
Conformity CE Low-Voltage Directive 73/23/EEC
Regulations EN 61800-3 Interference level B
Climatic conditions Air humidity max. 90 % without condensation
Cooling Passively via housing surface and rear panel
Permissible temperature ranges
Transport -25 °C... +70 °C
Storage -25 °C... +70 °C
Operation 0 °C ... +50 °C above +40 °C, reduce the power by
20 W/°C
Permissible installation height 0 ... 1000 m amsl above 1000 m amsl, reduce the rated
output current by 5 %/1000 m
Mounting position Vertical
Mounting clear ances
above/below 100 mm
sidewise Directly alignable
Monitoring Overvoltage / undervoltage in the DC bus, overcurrent or
short circuit of the output stage, motor temperature and
output stage temperature, I
2x
t-monitoring of the motor,
encoder monitoring
Type of protection IP 20
Inputs 6 digital inputs, 2 analog inputs
(adjustable via software)
Outputs 2 digital outputs, 2 analog outputs
(adjustable via software)
Bus system CAN (DS301, DSP402)
Memory cards Multimedia card