Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Transfering parameters to other standard devices
2
19
EDKVF93−05 EN 1.0
Copying parameter sets from the keypad to the standard device
Step Key
sequence
Action
1. Connect keypad to controller 2
2. Inhibit controller Terminal X5/28 = LOW
The "IMP" status display illuminates.
The drive coasts
3. Disconnect connectors X5 and X6 All control terminals have the defined "LOW" state.
4. On the "Load/Store" menu select
C0002
On the "Load/Store" menu select code C0002 "PAR
LOAD" using the arrow keys.
5. Change to the parameter level
The active parameter set is displayed, e. g. display "0"
and "Load Default"
6. Select the correct copy function The settings stored in the controller are overwritten.
l Copy all available parameter sets to the
controller and save in non−volatile memory.
The parameters are not yet active after copying. Select
parameter set and load into main memory. ! 17
Set "20" "ext −> EEPROM"
l Copy individual parameter sets to main memory.
Copy parameter set 1:
ð Set "11" "Load ext PS1"
Copy parameter set 2:
ð Set "12" "Load ext PS2"
Copy parameter set 3:
ð Set "13" "Load ext PS3"
Copy parameter set 4:
ð Set "14" "Load ext PS4"
7. Start copying
The "RDY" status display goes off. "BUSY" is indicated
as parameter value.
When "BUSY" goes off, all selected parameter sets
have been copied to the controller. The "RDY" status
display illuminates.
8.
Change to the code level
A
Display of the operating level
B
Display of C0002 and "PAR LOAD"
9. Save individually copied parameter
sets in non−volatile memory
On the "Load/Store" menu select code C0003 "PAR
SAVE" using arrow keys and save contents of the main
memory in non−volatile memory.
10. Connect connectors X5 and X6
11. Enable controller Terminal X5/28 = HIGH
The drive runs with the new settings.
efesotomasyon.com - Lenze