Technical data
Standards and operang condions
Conformies/approvals
Conformity and approval
CE 2014/30/EU EMC Direcve
Applied harmonised standards:
EN 61000-6-2:2005 + AC:2005
EN 61000-6-4:2007 + A1:2011
EN 55024:2010
RoHS 2011/65/EU RoHS Direcve
Applied harmonised standards:
EN 50581:2012
Protecon of persons and device protecon
Protecon of persons and device protecon
Degree of protecon EN 60529 IP 20
Electrical isolaon
To the eldbus Depending on the eldbus network used
PE-GND 110 VDC
PE-24V 110 VDC
Protecve measure Internal polarity reversal protecon against short circuit/
overvoltage
EMC data
EMC
Interference emission EN 61000-6-4 Class A (industrial premises) interference radiaon (30…6 GHz)
7.3 of CISPR 16-2-3 +A1 +A2 2010/2014
EN 61000-6-3 Class A (industrial premises) conducted interference (0.15…30
MHz) EN 55022:2010/AC:2011
Immunity to interference EN 61000-6-2 Industrial premises
IEC 61000-4-2 Immunity to interference against the discharge of stac
electricity EN61000-4-2 2009 ESD; severity 3, i.e. 8 kV with air
discharge, 4 kV with contact discharge
IEC 61000-4-3 Immunity to interference against high-frequency
electromagnec elds EN61000-4-3 +A1 +A2 2006/2008/2010
RF interference (housing) 80 MHz … 1000 MHz, 10 V/m 80 % AM
(1 kHz)
IEC 61000-4-4 Immunity to interference against fast, transient electrical
interference/burst EN61000-4-4 +A1 2004/2010 burst, severity 3
IEC 61000-4-5 Immunity to interference against fast transients EN61000-4-5
2006 surge, severity 1
IEC 61000-4-6 Immunity to interference against conducted interference
EN61000-4-6 2009 150 kHz … 80 MHz, 10 V/m 80 % AM (1 kHz)