Configuration of analog and digital setpoints and actual values
Analog setpoints via terminal
10
Function library
10.8
10.8.2
L
10.8-4
EDS82EV903-1.0-11/2002
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0430* Automatic analog 0
0 not active
Gain and offset are calculated by two points
^ 10.8-3
v
input adjustment
1 Input point for X3/1U, X3/1I
from the setpoint characteristic. Choose
(A)
2 Input points for X3/2U, X3/2I
two points distant from each other to
C0431*
v
(A)
Coordinates point 1 -100.0 {0.1 %} 100.0
.
1. Select and input under C0430 which you
want to calculate gain and offset for
2. Enter point 1 under C0431 X value
1 X(P1) -100.0 Analog setpoint of P1
100 % = max. input value (5 V, 10 V or 20 mA)
(setpoint) and Y value (output frequenc y)
2 Y(P1) -100.0 Output frequency of P1
100 % = C0011
3. Enter point 2 under C0432 X value
(setpoint) and Y value (output frequenc y)
C0432*
v
(A)
Coordinates point 2 -100.0 {0.1 %} 100.0
.
u
v
u
u
y
entered under C0413 (offset) and C0414
(gain)
1 X(P2) 100.0 Analog setpoint of P2
100 % = max. input value (5 V, 10 V or 20 mA)
2 Y(P2) 100.0 Output frequency of P2
100 % = C0011