Operation with increased rated power
Rated data for mains voltage 400 V
4
Technical data
4.4
4.4.2
L
4.4-8
EDS82EV903-1.0-11/2002
Operation without mains choke
Installatio n t o EN 60204-1 Installation to UL
1)
8200 vector Mains L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV551K4C 0.55 M6 A B6 A 1 5A 18
E82EV751K4C 0.75 Operation only with mains choke
E82EV222K4C 2.2 Operation only with mains choke
≥ 300 m
2)
E82EV302K4C 3.0 M16 A B16 A 2.5 15 A 14
≥ 30 mA
3)
E82EV402K4C 4.0 Operation only with mains choke
E82EV752K4C 7.5
3
PE
C
Operation only with mains choke
E82EV153K4B 15
320 ... 440 V;
E82EV223K4B 22
45 ... 65 Hz
E82EV303K4B 30
E82EV453K4B 45 Operation only with mains choke
E82EV553K4B 55
E82EV753K4B 75
E82EV903K4B 90
Operation with mains choke
Installatio n t o EN 60204-1 Installation to UL
1)
8200 vector Mains L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV551K4C 0.55 M6 A B6 A 1 5A 18
E82EV751K4C 0.75 M6 A B6 A 1 5A 18
E82EV222K4C 2.2 M10 A B10 A 1.5 10 A 16
≥ 300 m
2)
E82EV302K4C 3.0 M10 A B10 A 1.5 10 A 16
≥ 30 mA
3)
E82EV402K4C 4.0 M16 A B16 A 2.5 15 A 14
E82EV752K4C 7.5
3
PE
C
M25 A B25 A 4 25 A 10
E82EV153K4B 15
320 ... 440 V; M50 A - 16 50 A 6
E82EV223K4B 22
45 ... 65 Hz
M63 A - 25 63 A 4
E82EV303K4B 30
M80 A - 25 80 A 3
E82EV453K4B 45 M125 A - 50 125 A 0 ≥ 300 mA
E82EV553K4B 55 M160 A - 70 175 A 2/0
E82EV753K4B 75 M160 A - 70 175 A 2/0
E82EV903K4B 90 M200 A - 95 200 A 3/0
Fuse
E.l.c.b.
1)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: Voltage 500 ... 600 V, tripping characteristic ”H” or ”K5”
2)
All-current sensitive e.l.c.b. for use with E82EVxxxK4C0xx
3)
All-current sensitive e.l.c.b. for use with E82EVxxxK4C2xx
Observe national and re gional regulations (e. g. VDE 0113, EN 60204)
Fuses and cable cross-sections
(operation with increased rated
power, mains voltage 400 V)