EasyManua.ls Logo

Lenze E82ZAFIC010 - Wiring according to EMC

Lenze E82ZAFIC010
31 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Electrical installation
Wiring according to EMC
EDK82ZAFIC−010 DE/EN/FR 4.052
H2_EMV_Verdraht−VorgehenVerdraht_EN
Wiring according to EMC
For wiring according to EMC requirements observe the following points:
ƒ Use an equalizing conductor with a cross−section of at least 16 mm
2
(reference: PE)
to avoid potential differences between the bus nodes.
ƒ Separate control/data cables from motor cables.
ƒ Connect the shields of control/data cables at both ends.
ƒ Observe the other notes concerning EMC−compliant wiring given in the
documentation for the standard device.
Wiring procedure
1. Observe the bus topology, do not use any stubs.
2. Follow the wiring notes given in the documentation for the control system.
3. Only use cables which comply with the specifications listed (54).
4. Observe the notes concerning the voltage supply of the function module (55).