4 Technical data
General Data
EDK82ZAFIC−010 DE/EN/FR 4.046
H1_Daten−Komm_Daten_E82ZAFICxxx
4 Technical data
General Data
Area Values
Order designation E82TAFIC010
Communication medium RS485
Network topology Ring (go and return line in the same cable)
Number of bus nodes Dependent on INTERBUS master (e.g. Phoenix Contact G4 master).
For the following data, which depend on whether PCP
communication is used or not, always the smaller value applies:
l with PCP communication: max. 62 or
l without PCP communication: max. 256/number of PCDs
Distance between two bus
nodes
Max. 400 m
INTERBUS identification
(ID code)
l With 1 word PCP: 227 (0xE3)
l Without PCP: 3 (0x03)
Drive profile DRIVECOM profile "Drive technology 20"
INTERBUS node Slave
Baud rate 500 kbps
Process data words (PCD),
16 bits
1 ... 4 words
Parameter data words (PCP),
16 bits
0 or 1 word
PDU length Max. 64 bytes
Supported PCP services
l Initiate
l Abort
l Status
l Identify
l Get−0V−long
l Read
l Write
Communication time
l Sum of the cycle time and the processing time in the bus nodes.
The times are independent of each other.
l Processing time in the standard device
Parameter data (PCP): approx. 30 ms + 20 ms tolerance
Process data (PCD): approx. 3 ms + 2 ms tolerance