Commissioning
Commissioning steps
7
EDK82ZAFIC−010 DE/EN/FR 4.0 61
H2_Inbetriebnahmeschritte−inbetrieb
Detailed
information
ProcedureStep
8. Select the function module as the source for control commands and
setpoints.
l Set C0005 = 200.
A preconfiguration for operation with the function module is
carried out.
This preconfiguration already links the control words and
status words.
9.
Use C1511 to assign the process data output words (POW) of the
master to the process data input words of the standard device.
Communication
Manual
INTERBUS
Lenze setting:
POW1: DRIVECOM control word (DRIVECOM CTRL)
POW2: Setpoint1 (NSET1−N1)
POW3: Setpoint2 (NSET1−N2)
POW4: Additional setpoint (PCTRL1−NADD)
10.
Use C1510 to assign the process data output words of the standard
device to the process data input words (PIW) of the master.
Communication
Manual
INTERBUS
Lenze setting:
POW1: DRIVECOM status word (DRIVECOM STAT)
PIW2: Output frequency with slip (MCTRL1−NOUT+SLIP)
PIW3: Output frequency without slip (MCTRL1−NOUT)
PIW4: Apparent motor current (MCTRL1−IMOT)
11. Enable process output data with C1512 = 65535.
Only required when C1511 has been changed.
12. Enable the standard device via terminal 28 (CINH).
l Apply HIGH level to terminal 28.
13. Select setpoint.
l The master transmits the setpoint via the selected process data
output word.
14. Change to the READY TO START state:
l The master transmits the DRIVECOM control word:
0000 0000 0111 1110
bin
(007E
hex
).
Communication
Manual
INTERBUS
15. The standard device has entered the READY TO START state.
l The master receives the DRIVECOM status word:
xxxx xxxx x01x 0001
bin.
16. Change to the OPERATION ENABLED state.
l The master transmits the DRIVECOM control word:
0000 0000 0111 1111
bin
(007F
hex
).
17. The drive starts up.