Technical data
General data and operating conditions
4
40
EDK94AZMP DE/EN/FR/ES/IT 8.0
4 Technical data
4.1 General data and operating conditions
Conformity and approval
EAC
TP TC 020/2011
(TR CU 020/2011)
Electromagnetic
compatibility of
technical means
Eurasian Conformity
TR CU: Technical Regulation
of Customs Union
TP TC 004/2011
(TR CU 004/2011)
On safety of low
voltage equipment
Eurasian Conformity
TR CU: Technical Regulation
of Customs Union
UR UL508 Industrial Control Equipment, Underwriter
Laboratories (File−No. E219022) for USA and Canada
Mains data
Mains types
With grounded neutral (TT/TN systems)
Operation permitted without restrictions
Other mains types Observe instructions for special measures in the
documentation for the basic device!
Protection of persons and equipment
Enclosure
EN 60529 IP20
Not in the wire range of the
terminals
NEMA 250 Protection against
contact to type 1
Earth leakage current IEC/EN 61800−5−1 > 3.5 mA AC
> 10 mA DC
Observe regulations and
safety instructions!
Insulation resistance IEC/EN 61800−5−1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II

Table of Contents