Installation
Electrical installation
Wiring with a host (master)
5
l
26
EDSMF2133IB EN 5.0
Bus cable length
The length of the bus cable depends on the baud rate used:
Baud rate [kbps] Length [m]
9.6 ... 93.75 1200
187.5 1000
500 400
1500 200
3000 ... 12000 100
) Note!
The baud rate depending on the data volume, cycle time, and number of nodes
should only be selected as high as required for the application.
I Tip!
For high baud rates we recommend to consider the use of optical fibres.
Advantages of optical fibres:
ƒ On the transmission path external electromagnetic interference remains
ineffective.
ƒ Bus lengths of several kilometres are also possible with higher baud rates.
The bus length
is irrespective of the baud rate.
depends on the optical fibre used.