Configuration
821XKlimaBA0399 7-11
Code IMPORTANTPossible settingsNameCode IMPORTANT
InfoSelectionLenze
Name
C126* Selection of
communication
errors
-0- -0- No TRIP when stopping the communication
in the process channel
-1- TRIP (-CEO-) when stopping the
communication in the process channel
Only for bus
operation
C127 Selection
Setpoint selection
-0- -0- Absolute setpoint selection in Hz via C046
or process channel
-1- Standardized setpoint selection via C141 (0
... 100 %)or process channel (
16384 =
f
dmax
(C011))
Only for bus
operation
C135* Control word see Operating
Instructions 2102
C141* Standardized
setpoint
-100.00 {0.01 %} 100.00 Only for bus
operation
Only when C127
=1active
C142
¤
Start condition -1- -0- Automatic start inhibited, flying-restart
circuit not active
-1- Automatic start, if term. 28 HIGH,
flying-restart circuit not active
-2- Automatic start inhibited, flying-restart
circuit active
-3- Automatic start, if term. 28 HIGH,
flying-restart circuit active
C144
Chopper-frequen
-1- -0- No chopper-frequency lowering
when
J
max
-10
C
C150* Status word see Operating
Instructions 2102
C156* Current threshold 0 0 {1 %} 150
C161* Current fault Only display
C162* Last fault Only display
C163* Last but one fault Only display
C164* Last but two fault Only display
C170
¤
TRIP-reset
selection
-0- TRIP-reset by pressing the STP key or LOW
signal at ctrl. enable
-1- Auto-TRIP reset
C171 Delay for
Aut o- TRIP- Rese t
0.00 0.00 {0.01s} 60.00
C178* Operating time Only display
C179* Mains switch-on
time
Only display