EasyManua.ls Logo

Lenze I95AE222F

Lenze I95AE222F
184 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Terminal data
Rated power P
r
ated
kW 0.37 ... 1.5
Connecon descripon Mains connecon
Connecon X100
Connecon type Pluggable
Max. cable cross-secon mm² 2.5
Max. cable cross-secon AWG 12
Stripping length mm 8
Stripping length in 0.3
Tightening torque Nm 0.5
Tightening torque lb-in 4.4
Required tool Screwdriver 0.5 x 3.0
Rated power P
r
ated
kW 0.37 ... 1.5
Connecon descripon PE connecon
Connecon PE screw
Max. cable cross-secon mm² 6
Max. cable cross-secon AWG 10
Stripping length mm 10
Stripping length in 0.4
Tightening torque Nm 2
Tightening torque lb-in 18
Required tool Torx key 20
Rated power P
r
ated
kW 0.37 ... 1.5
Connecon descripon Motor connecon
Connecon X105
Connecon type Pluggable
Max. cable cross-secon mm² 2.5
Max. cable cross-secon AWG 12
Stripping length mm 8
Stripping length in 0.3
Tightening torque Nm 0.5
Tightening torque lb-in 4.4
Required tool Screwdriver 0.5 x 3.0
The terminal data for the terminal X1 can be found under:4Basic Sa
fety - STO ^ 161
The terminal data for the terminals X82 and X83 can be found under: 4Terminal data ^ 165
Electrical ins
tallaon
Mains connecon
1-phase mains connecon 230/240 V
136

Table of Contents

Related product manuals