Fusing data
A residual current device (RCD) is oponal.
Fusing da
ta for UL/NEC compliant installaons: 4Fusing data ^ 131
Inverter Fuse Circuit breaker RCD
Max.
SCCR
Characterisc
Max. rated
curr
ent
Max.
SCCR
Characterisc
Max. rated
current
Type
kA A kA A mA
I95AE137D gG/gL, gRL 10 B 10 ≥30 Typ B
I95AE155D gG/gL, gRL 10 B 10 ≥30 Typ B
I95AE175D gG/gL, gRL 16 B 10 ≥30 Typ B
I95AE215D gG/gL, gRL 16 B 16 ≥30 Typ B
I95AE222C gG/gL, gRL 16 B 16 ≥30 Typ B
I95AE240C gG/gL, gRL 50 B 50 ≥300 Typ B
I95AE255C gG/gL, gRL 50 B 50 ≥300 Typ B
Electrical ins
tallaon
Mains connecon
3-phase mains connecon 230/240 V