Single-axis controllers
Wiring
Devices in the range 2 ... 24 A (0.37 ... 11 kW)
4
112
EDS94SPP101 EN 7.1
How to proceed:
1. Strip the motor cable according to dimensions given.
2. Fold back the shield of the motor cable over the cable sheath.
3. Stabilise the shield with self-adhesive conductive foil (recommendation).
4. Fix the shield and conductive foil with heat-shrinkable tube on the cable sheath.
5. Fasten cable lugs or wire end ferrules.
6. Connect the shields separately to the shield sheet using shield clamps (no strain
relief).
E94AZJS-013