Single-axis controllers
Wiring
Devices in the range 145 ... 695 A (75 ... 370 kW)
4
124
EDS94SPP101 EN 7.1
Mains
Terminal X100 Marking Description
L1
L2
L3
Connection of the mains phases L1, L2, L3
SSP94KL0X8
Connection for the PE conductor on the supply side with M8 ring
cable lug
Terminal data
Max. conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Device size 8S:
Flexible
With wire end ferrule
95
000 14 124 Inbus 5
M8 ring cable lug 95 000 9.5 84 WAF 13
Motor temperature monitoring
Terminal X106 Labelling Description
T1
T2
Motor temperature monitoring with PTC element (type-A sensor,
switching performance according to EN 60947-8 for type-A tripping units)
or thermostat (NC contact).
SSP94X6106
Terminal data
Max. conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Flexible
2.5
12 0.5 ... 0.6 4.5 ... 6.2
Slot
0.6 x 3.5
With wire end ferrule