Single-axis controllers
Control terminals
4
141
EDS94SPP101 EN 7.1
Terminal X2 Labelling Description
GE GND external supply
24E 24 V external supply via a safely separated power supply
unit (SELV/PELV) (only required for mains-independent supply of the
control electronics)
9400SSP000X2
SB State bus in/out (reference GE)
Terminal data
Conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Flexible
0.2 ... 2.5
24 ... 12 Spring terminal
With wire end
ferrule
Electrical data
24 V
Rated voltage 24 V
According to IEC 61131-2
Voltage range 19.2 ... 28.8 V
Residual ripple max. ± 5 %
Current consumption Approx. 1.2 A during operation
Max. 3 A starting current for 100 ms
Fuse Circuit breaker with tripping
characteristic B or C,
Standard blade-type fuses
Looping through
Max. 12 devices with 2.5 mm
2
Fusing: 16/15 A
Max. 8 devices with 1.5 mm
2
Fusing: 10/10 A
Connectable cross-cuttings See terminal data