Loading...
Power supply modules
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 400 V
6
221
EDS94SPP101 EN 7.1
6.3.2 Operation at rated mains voltage 400 V
Basis of the data
Mains Voltage Voltage range Frequency range
U
LN
[V] U
LN
[V] f[Hz]
3/PE AC 400 320-0%...440+0% 45-0%...65+0%
Input data
Voltage Frequency Current [A]
Number of
phases
[V] [Hz] max. +45 °C c max. +55 °C c
E94APNE0104 400 50/60 8 6 3
E94APNE0364 400 50/60 29 21.8 3
E94APNE1004 400 50/60 82 61 3
E94APNE2454 400 50/60 200 150 3
c Temperature in the control cabinet
Voltage Continuous input power
Type [V] S
L
[kVA]
E94APNE0104 400 5.5
E94APNE0364 400 20.1
E94APNE1004 400 56.7
E94APNE2454 400 138
Output data
Basis of the data
Mains Voltage
U
DC
[V]
Voltage range
U
DC
[V]
Frequency range
f[Hz]
2/PE DC 565 455-0%...620+0% -
Voltage Frequency Current [A]
Number of
phases
[V] [Hz] max. +45 °C c max. +55 °C c
E94APNE0104 565 0(DC) 10 7.5 2
E94APNE0364 565 0(DC) 36 27 2
E94APNE1004 565 0(DC) 100 75 2
E94APNE2454 565 0(DC) 245 184 2
c Temperature in the control cabinet