Power supply modules
Control terminals
6
258
EDS94SPP101 EN 7.1
24 V supply
The devices can only function correctly when the 24-V supply is switched on!
E94APNE0104 and E94APNE0364:
Terminal X11 Labelling Description
GE GND external supply
SSP9400X11
24E 24 V external supply through safely separated power supply unit
(SELV/PELV)
IEC 61131-2, 19.2 ... 28.8 V, residual ripple max. ±5 %
Current during operation: 450 mA
Starting current: 4 A for 100 ms
Terminal data
Conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Flexible
0.2 ... 2.5
24 ... 12 Spring terminal
With wire end
ferrule
Stripping length / contact length: 10 mm
E94APNE1004 and E94APNE2454:
Terminal X11 Labelling Description
GE GND external supply
24E 24 V external supply through safely separated power supply unit
(SELV/PELV)
IEC 61131-2, 19.2 ... 28.8 V, residual ripple max. ±5 %
Current during operation: 1.4 A
Starting current: 4 A for 100 ms
9400SSP000X2
SB Reserved
Terminal data
Conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Flexible
0.2 ... 2.5
24 ... 12 Spring terminal
With wire end
ferrule
Stripping length / contact length: 10 mm
State bus
Power supply modules are not designed as nodes on the state bus of the controller.