DC-bus operation
Rated data
DC fuses
8
326
EDS94SPP101 EN 7.1
Fuse the individual +UG/-UG cables to protect the DC-bus connection. The DC-bus
connection is protected against damage through a DC earth fault or short circuit in a
device.
Controller/DC fuse assignment
Type
Rated value Type Size Number per
[A] (SIBA) [mm] or size +UG/-UG
Multi Drives
E94AMxE0024
E94AMxE0034
E94AMxE0044
20
EFSGR0200AYHz 14 x 51
1
EFSGR0200AYIz 22 x 58
E94AMxE0074
E94AMxE0094
32
EFSGR0320AYHz 14 x 51
EFSGR0320AYIz 22 x 58
E94AMxE0134
E94AMxE0174
63 EFSGR0630AYIz 22 x 58
E94AMxE0244
E94AMxE0324
100 EFSGR1000AYIz 22 x 58
Single Drives
E94ASxE0024
E94ASxE0034
16
EFSGR0200AYHz 14 x 51
1
EFSGR0200AYIz 22 x 58
E94ASxE0044
E94ASxE0074
32
EFSGR0320AYHz 14 x 51
EFSGR0320AYIz 22 x 58
E94ASxE0134
E94ASxE0174
63 EFSGR0630AYIz 22 x 58
E94ASxE0244
E94ASxE0324
E94ASxE0474
100
EFSGR1000AYIz 22 x 58
EFSGR1000ANVN NH1
E94ASxE0594
E94ASxE0864
200 EFSGR2000ANVN NH1
E94ASxE1044 250 EFSGR2500ANWN NH2
E94ASxE1454 350 EFSGR3500ANWN NH2
E94ASxE1724
E94ASxE2024
400 EFSGR4000ANWN NH2
E94ASxE2454 500 EFSGR5000ANWN NH2
E94ASxE2924 350 EFSGR3500ANWN NH2
2 (in parallel)
E94ASxE3664 400 EFSGR4000ANWN NH2
E94ASxE4604 500 EFSGR5000ANWN NH2
E94ASxE5724 400 EFSGR4000ANWN NH2
3 (in parallel)
E94ASxE6354
500 EFSGR5000ANWN NH2
E94ASxE6954
Tab. 8-7
z K = indicator, N = no indicator