Single-axis controllers
General data and operating conditions
4
40
EDS94SPP101 EN 7.1
”Single Drive”
supply conditions
AC-mains operation
Direct connection
DC-bus operation Direct connection via terminals or busbars(can be retrofitted)
For more information, please see the chapter DC-bus
operation.
Power systems
TT
Operation permitted without restrictions.
TN
With grounded phase Operation with additional measures permitted:
z Overvoltage must be reduced to overvoltage category II
according to EN 61800-5-1.
z Measures described for IT systems must be applied.
IT Additional device-internal measure required (see (”Earthing
of internal EMC filters”, 103)
Motors EN 60034 Only use motors suitable for inverter operation. Insulation
resistance: max. û 1.5 kV, max. du/dt 5kV/μs
Operating conditions
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1 1K3 (-25 ... +60 °C)
Transport IEC/EN 60721-3-2 2K3 (-25 ... +70 °C)
Operation IEC/EN 60721-3-3 3K3 (-10 ... +55 °C)
Current derating at +45 ... +55 °C:
Device size 1 ... 7: 2.5 %/°C
Device size 8S ... 10: 1 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m
Pollution EN 61800-5-1 Degree of pollution 2
Vibration resistance (9.81 m/s
2
=1g)
Transport
IEC/EN 60721-3-2 2M2
EN 61800-2
2...9Hz:amplitude3.5mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd 5...13.2Hz:amplitud1mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
IEC/EN 60068-2-6
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g