Commissioning
Important notes
NOTICE
Do not brake the motor by short-circuit operaon.
Short-circuit braking may damage the motor.
Before inial switch-on
That the drive does not show any visible signs of damage.
Is the mechanical xing o.k.?
Has the electrical connecon been implemented correctly?
Are all rotang parts and surfaces that may become hot protected against contact?
Is the featherkey radially secured during the test run without output elements?
Have all screwed connecons of the mechanical and electrical parts been ghtened?
Is it ensured that the cooling air can be freely supplied and discharged?
Has the PE conductor been connected correctly?
Have the protecve devices against overheang (temperature sensor evaluaon) been
acvated?
Is the inverter parameterised correctly for the motor? (See operang instrucons for the
inverter)
Are the electrical connecons ok?
Is the phase sequence of the motor connecon correct?
Is a protecon against contact provided in front of rotang parts and in front of surfaces
that can get hot?
Is the contact of good electrical conducvity if a PE connecon on the motor housing is
used?
Before inial switch-on, aer a longer downme or aer overhaul of the motor, check the
insulaon resistance because condensed water may have formed.
With values ≤1 kΩ per volt of rated voltage, the insulaon resistance is inadequate and no
voltage may be applied.
Dry the winding unl the insulaon resistance is >1 kΩ per volt of the rated voltage.
Funconal test
Aer commissioning, check all individual funcons of the drive:
Rotang direcon in decoupled state.
Torque behaviour and current consumpon
Funcon of the feedback system
Brake funcon
During operaon, carry out inspecons on a regular basis. Pay special aenon to:
Unusual noises
Irregular running
Increased vibraon
Loose xing elements
Condion of electrical cables
Speed variaons
Deposits on the drive system and in the cooling channels