Mains connecon QUICKON connector
Motor MSEMA☐☐063-42 MSEMA☐☐080-32
Connecon X3
Laying system B2
Connecon type QUICKON connector
cable
cross-secon
Typ.
mm
2
1.0 1.5
Min.
mm
2
1.0 2.5
Max.
mm
2
1.0 2.5
Connecon for group drive according to EN 60204-1
L1
L2
L3
N
PE
F1 … F3
K
M
3~
+
A
1
I
N1
PE L1 L2 L3
M
3~
+
A
2
I
N2
PE L1 L2 L3
M
3~
+
A
3
I
N3
PE L1 L2 L3
M
3~
+
A
4
I
N4
PE L1 L2 L3
M
3~
+
A
n
I
Nn
PE L1 L2 L3
Max. total rated mains currents at 40 °C
Cable installaon in compliance
with
EN 60204-1
Laying system B2
cable
cross-secon
mm
2
1.5 2.5
I
N1
+ L
N2
+ I
N3
+ I
Nn
A 7.6 12.2
Fuse
Characteriscs gG/gL
Typ. rated current A --- ---
Max. rated current A 10 16
Circuit breaker
Characteriscs gRL
Typ. rated current A --- ---
Max. rated current A 10 16
4Mot
or data ^ 67
•
Use of c
opper cables insulated with PVC
•
Conductor temperature < 70 °C, ambient temperature < 40 °C
•
No bundling of cables or wires, thee wires under load.
•
Typical ulisaon 80 %
Mounng/
installaon
Electrical installaon
Mains connecon
61