Mains connecon with QUICKON connector
Motor MSEMA☐☐063-42 MSEMA☐☐080-32
Connecon X3
Connecon type QUICKON connector
cable
cross-secon
Typ. AWG 14 14
Min. AWG 16 16
Max. AWG 14 14
Connecon for group drive according to UL 61800-5-1
L1
L2
L3
N
PE
F1 … F3
K
M
3~
+
A
1
I
N1
PE L1 L2 L3
M
3~
+
A
2
I
N2
PE L1 L2 L3
M
3~
+
A
3
I
N3
PE L1 L2 L3
M
3~
+
A
4
I
N4
PE L1 L2 L3
M
3~
+
A
n
I
Nn
PE L1 L2 L3
Max. total rated mains currents at 40 °C
Cable installaon in compliance
with
UL 61800-5-1
Laying system
cable
cross-secon AWG 16 14
I
N1
+ L
N2
+ I
N3
+ I
Nn
A 8.0 12.0
Fuse
Characteriscs
Typ. rated current A --- ---
Max. rated current A 10 15
Circuit breaker
Characteriscs
Typ. rated current A --- ---
Max. rated current A 10 15
4Mot
or data ^ 67
•
Use UL-appr
oved cables:
•
Conductor temperature < 75 °C, ambient temperature < 40 °C
•
Typical ulisaon 80 %
•
Operaon from mains supply 5 kA rms SCCR:
•
Use current-liming UL-approved fuses (UL 248) or automac circuit breakers (UL 489),
v
oltage ³ 480 V.
•
Operaon from mains supply 200 kA rms SCCR:
•
Use current-liming UL-approved fuses (UL 248), current liming rang von 200 kA rms to
max. 5 kA rms, e.g. 15 A class CC.
•
It must be ensured that the Lenze Smart Motor is not installed in a control cabinet.
Mounng/
installaon
Electrical installaon
Mains connecon