Single drive connecon according to EN 60204-1
L1
3/N/PE AC 400/480 V
L1
L2
L3
N
PE
F1 … F3
L2
L3
SELV/PELV
DC 24 V
(+19.2 … +28.8 V)
5.6k
5.6k
R
b
M
3~
Rb1 Rb2
V
U
W
+
+
X3
X4
+
1 2 3
BD1BD2
X2
1 2 3
4
X1
1 2 3
4
X5
max. 50 mA
X6
GND
-I
DI1DI2
n. c.
5.6k
GND
-O
DO1DI324V
DC
AC
Q
400
1
23
4 1
23
4
Rb1 Rb2
X4
R
b
Rb1 Rb2
390
L1
F1 … F3
L2
L3
+
+
X3
Q
2
3
A
B
1
+
GND is bridged if the "DI/DO−GND bridged" version is specied on the nameplate.
Fuse data (F1 ... F3)
Motor MSEMA☐☐063-42 MSEMA☐☐080-32
Cable installaon in
compliance with
EN 60204-1
Installaon method B2
Fuse
Characteriscs gG/gL
Typ. rated current A 6 10
Max. rated current A 16 16
Semiconductor fuse
Characteriscs gRL
Typ. rated current A 6 10
Max. rated current A 16 16
Circuit breaker
Characteriscs C
Typ. rated current 6 10
Max. rated current A 16 16
Use of copper cables insulated with PVC
Conductor temperature < 70 °C, ambient temperature < 40 °C
No bundling of cables or wires, thee wires under load
Electrical installaon
Mains connecon
Connecon according to EN