EasyManua.ls Logo

Lenze SMVector - Page 51

Lenze SMVector
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
50
SV01N_13418587 EN/DE/ES/FR/IT/PT
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Segment #9
P750
Segment #9
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
P751
Segment #9
Accel/Decel Time
20.0 0.0 {sec} 3600.0
P752
Segment #9
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
P753
Segment #9
Digital Output State
0
Value set in P753 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
P754
Segment #9 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #10
P755
Segment #10
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
P756
Segment #10
Accel/Decel Time
20.0 0.0 {sec} 3600.0
P757
Segment #10
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
P758
Segment #10
Digital Output State
0
Value set in P758 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must
be set to accept data from the sequencer:
P140, P142, P441 = 27
P759
Segment #10 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #11
P760
Segment #11
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
P761
Segment #11
Accel/Decel Time
20.0 0.0 {sec} 3600.0
P762
Segment #11
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
P763
Segment #11
Digital Output State
0
Value set in P763 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
P764
Segment #11 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com