EasyManua.ls Logo

Leviton 2R208-21 - Preparation; List of Materials; Mounting the Enclosure; Selecting a Mounting Location

Leviton 2R208-21
69 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
3 INSTALLATION INSTRUCTIONS
3.3 Preparation
Verify the model number and electrical specifications of the device being installed
to confirm they are appropriate for the intended electrical service (see Section 2).
Consult local codes for any possible permits or inspections required before
beginning electrical work.
Ensure the conduit for the installation is appropriate for the intended application.
UL Type 4x conduit and conduit fittings are required for outdoor applications.
Make sure all tools to be used during installation have proper insulation ratings.
Look at the meter and inside the electrical panel for possible exposed wire, broken
wire, damaged components or loose connections.
3.4 List of Materials
Series 1000 or Series 2000 meter, enclosure, and associated mounting materials
Line 1, Line 2, Line 3 and Neutral hookup wires, as needed for the electrical
service
Wires must be 18 AWG or larger and insulated for 600 VAC min. Meter terminals
will accept wiring up to 14 AWG.
Current Transformers (CTs): This product is designed for use with Leviton 100mA
series of solid and split core CTs.
Conduit and fittings, as appropriate. UL Type 4X conduit and fittings must be used
for outdoor applications to maintain the rating of the installation.
3.5 Mounting the Enclosure
3.5.1 Selecting a Mounting Location
Series 1000 and 2000 meters require a switch or circuit breaker as part of the
building installation.
The switch or circuit breaker must be marked as the disconnecting device for
the meter.
It is recommended that the enclosure be mounted near the disconnecting device
in an area with adequate ventilation.
The enclosure should not be positioned in a manner that makes it difficult to
operate the disconnecting device.
Ensure that the CT and voltage lead lengths (and conduit lengths) are capable
of reaching the enclosure from the load center.
If a suitable mounting location near the load center cannot be found, additional
in-line fuses or circuit breaker may be required in accordance with
NEC regulations.
WEB VERSION

Table of Contents

Related product manuals