Properly installed meters with sound connections and secure conduit fittings should
not require user maintenance. If the meter is functioning abnormally, consult the FAQ /
Troubleshooting guide. If the answer cannot be found there, contact Leviton technical support.
5 TROUBLESHOOTING / FAQ
Solution
• Check to make sure all connections are wired.
• Test the voltage being supplied to the meter,
using an AC voltmeter.
• With power off, remove any additional in-line
fuses and test the circuit with the appropriate test
equipment.
• Verify CT connections and orientations.
• Make sure there is sufficient load to draw a
significant current.
• Test the voltage being supplied to the meter,
using an AC voltmeter.
• Check to make sure the reverse phase LED is
not on.
• Even if the reverse phase light is off, double-
check CT orientations. One CT installed in the
incorrect direction does not always illuminate the
reverse phase LED.
• Make sure that current and voltage connections
are in-phase.
• Check power connections and fuses.
• Verify orientation and connection of CT wires.
• Ensure that phasing is correct (CT1 on Line 1,
CT2 on Line 2).
• Verify that a load drawing more than 1 Amp is
connected to the meter.
Problem
1. LCD Display not on
2. Load LED not flashing
3. Registered consumption low
4. Reverse phase LED illuminated