4. Reattach the high-voltage cover.
PUSH
5. Connect CT and communications wires.
White (+)
Black or Brown (-)
Bare (RŌC) (S)
CT Connections (x3)
RS-485
USB-C Ethernet
Connecting Voltage
Connect the voltage leads (L1, L2, L3, and N, as necessary) to the meter through a
dedicated disconnect or circuit breaker. A voltage lead of 14 AWG THHN minimum
600V AC rating (or equivalent) is required.
NOTE: Verify the circuit breaker is marked as the disconnect breaker for the meter.
N
L1 L2 L3
5 METER INSTALLATION