LG Air-Cooled Heat Pump Inverter Scroll Chiller Installation and Owners Manual
OPTIONAL SETTINGS
Description
Screen Display
(1 Level)
Detail Description
Start/Stop RUN /STOP
Set RUN to operate the product and STOP to stop the
operation.
Cooling/Heating HEAT/COOL
Sets the product’s Cooling/Heating Operation Mode.
COOL selects Cooling Mode and HEAT selects Heat-
ing Mode.
Cooling setpoint tem-
perature
7 Sets Cooling Target Temperature. (4 °C~ 20 °C)
Heating setpoint tem-
perature
45 Sets Heating Target Temperature.(30 °C~ 55 °C)
Load outflow water
Temperature
-
Shows the temperature value of Load outflow water.
(Specified in 0 Level)
Control Mode LOC/DIST/SCHE
Set’s the product’s Control Mode. In LOC, the product
control is available with HMI and Chiller Controller.
DIST refers Remote Control Mode. In SCHE, the prod-
uct is controlled following the schedule set at HMI.
Remote Mode CONT/BUS
Sets how to set in Remote Mode. CONT enables the
product’s operation mode by simple switch contacts.
BUS enables the control on the entire product through
communication from other communication devices.
Central Control
Address
1
The product address can be set for communication
with other communication devices. The address can
be set by selecting values from 1-247.
Maximum Operation
Frequency
110
Sets the Maximum Operation Frequency.(70 Hz~130
Hz)
Capacity of product -
Shows the current Capacity of product.
(Specifies in 0 Level)
Version -
Shows the program information of Chiller Controller
installed in the current product as Version. Version
information is subjected to change for improvement of
the product performance or the quality improvement.
(Specifies in 0 Level)

Related product manuals