Function
2.2 Defrost
Starting Condition
Starting defrost control if one case of bellowing cases is satisfied
[1] 1-UNIT Model
a) air temp. ≥ 0°C : hex pipe temp. < -7°C
b) -5°C < air temp. < 0°C : hex pipe temp. < (air temp.-8°C)
c) air temp. ≤ -5°C : hex pipe temp. < (air temp. -11°C)
[2] 2 & 3 UNITS Model
1) Partly defrost
When there is one or more bellowing cases of hex pipe temp. as each unit
a) air temp. ≥ 0°C : hex pipe temp. < -10°C
b) air temp. < 0°C : hex pipe temp. < (air temp.-11°C)
2) All defrost
When all hex pipe temp. is satisfied bellowing cases
a) air temp. ≥ 0°C : hex pipe temp. < -7°C
b) -5°C < air temp. < 0°C : hex pipe temp. < (air temp._8°C)
c) air temp. ≤ -5°C : hex pipe temp. < (air temp. -9°C)
■ Comp. combination during oil return control