Function
2.4 Stopping operation
2.4.1 Stopping operation on cooling mode
2.4.2 Stopping operation on heating mode
Inv Compressor
Fan
Main EEV
4way valve
Subcooling EEV
0Hz
0Hz
Full open
On
Full close Full close
OperationComponent
After 15 min from stop, min.
After 15 min from stop, off
Note
Sub unit
compressor
Off
Hot gas bypass On After 15 min from stop, Off
Inv Compressor
Fan
Main EEV
4way valve
Subcooling EEV
0Hz
0Hz
Full open
Off
Full close Full close
OperationComponent
After 15 min from stop, min.
Off
-
-
-
-
-
-
Note
Sub unit
compressor
Off
Hot gas bypass On After 15 min from stop, Off