Function
3.1 Pressure protection control
3.1.1 Pressure control on cooling mode
High pressure control
Low pressure control
3. Protection control
StopStopPd 3676 kPa
OffNormal control
Pd < 3284 kPa
Normal controlFrequency holdingPd 3284 kPa
+10Hz/2sec.-5Hz/2sec.Pd > 3546 kPa
Hot gasFanCompressorPressure Range
Frequency
holding
Normal controlPs 242 kPa
OffNormal control
Ps 399 kPa
On
-10Hz/2sec.-5Hz/2sec.
Ps 229 kPa
before
1min
StopStop
Ps 229 kPa
after 1min
Hot gasFanCompressor
Pressure Range