Troubleshooting Guide
- 266 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Error diagnosis and countermeasure flow chart
1. Bad connection of air temperature connector
2. Defect of air temperature connector(Open/Short)
3. Defect of outdoor PCB
1. Bad connection of air temperature connector
2. Defect of air temperature connector(Open/Short)
3. Defect of outdoor PCB
1. Bad connection of air temperature connector
2. Defect of air temperature connector(Open/Short)
3. Defect of outdoor PCB
Error No. Error Type Error Point Main Reasons
Abnormal value of
sensor (Open/Short)
Abnormal value of
sensor
(Open/Short)
Abnormal value of
sensor (Open/Short)
Sensor error of
outdoor air temper-
ature
Piping temperature
sensor error of heat
exchanger in
main & sub outdoor
unit heat exchanger
(A,B)
Compressor suc-
tion temperature
sensor error
44 (Main)
118 (Sub1)
130 (Sub2)
159 (Sub3)
46 (Main)
120 (Sub1)
132 (Sub2)
161 (Sub3)
45 (Main H/E A)
48 (Main H/E B)
123 (Sub1 H/E A)
124 (Sub1 H/E B)
135 (Sub2 H/E A)
136 (Sub2 H/E B)
164 (Sub3 H/E A)
165 (Sub3 H/E B)
Is sensor connected
to PCB correctly??
Is sensor value correct?*
Connect sensor to PCB correctly
Replace sensor
Replace corresponding
outdoor unit PCB
Yes
No
No
Yes
* If value is 100k (open) or 100 Ω↓(short), error occurs
NB: Resistance value of temperature sensor change according to
temperature
It is normal if value shown as below (±5% error)
Sensor of air temperature: 10°C = 20.7k : 25°C= 10k : 50°C= 3.4k
Sensor of piping temperature: 10°C = 10k : 25°C= 5k : 50°C= 1.8k
Refer to CH41
Refer to CH45
Error No. Error Type Error Point Main Reasons
Abnormal value of
sensor (Open/Short)
Abnormal value of
sensor (Open/Short)
Discharge piping
temperature sensor
error of constant
compressor (Main
unit)
Piping temperature
sensor error of heat
exchanger in main
& sub outdoor unit
heat exchanger (B)
47
(constant com-
pressor of main
outdoor unit)
48
(Heat exchanger B)