EasyManua.ls Logo

LG ARNU Series - Page 287

LG ARNU Series
338 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting Guide
- 287 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. HR units power cable or transmission cable connection
defect
2. After Auto-Addressing, wrong address setting of the
indoor unit (Defective indoor power / transmission error
and PCB defect)
3. Wrong setting of the HR units rotary switch or dip switch
4. HR unit PCB defect
Error
No.
Error Type Error Point Main Reasons
After the Auto operation,
if the number of the
indoor units detected is
different from the number
communicating indoor
unit
Pipe detection error200
HR: Heat Recovery
1) Check the periodic blinking of the HR units green LED (transmission LED )
2) When green LED (transmission LED) of HR unit blinks regularly,
2.1) Check input power of HR unit.(220V±10%)
2.2) After reset of power of outdoor, wait for more than 30 minutes, temperature of pipes will be cool down then,
Do Auto-Addressing
2.2) While power of HR unit is on, check total indoors display CH05 or not.(Refer to CH05)
3) When green LED (transmission LED) of HR unit blinks regularly, Check setting of rotary switch and Dip switch,
After reset of power of outdoor and HR unit, wait for more than 30 minutes, temperature of pipes will be cool
dow then, Do Auto-Addressing *
4) If indoor unit quantity is different between installed quantity and quantity which check thru piping searching,
check pipe installation condition
Outdoor unit HR unit Indoor unit
5) If indoor unit has not been connected to #1 valve of HR unit, set pipes of HR unit manually**
6) If it is not applied as above, set pipes of HR unit as manual
[NB] How to check display method of outdoor Main PCB 7-segment ?:
'88' Indoor qty which check thru 'Auto-Addressing' '88' Indoor qty which check thru piping checking'