Troubleshooting Guide
- 293 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Defective temperature sensor connection
Defective temperature sensor
(Open/Short)
Defective outdoor unit PCB
Error No. Error Type Error Point Main Reasons
Abnormal value of sensor
measurement (Open / Short)
HR unit liquid pipe tem-
perature sensor error
201(HR unit1)
205(HR unit2)
209(HR unit3)
213(HR unit4)
217(HR unit5)
221(HR unit6)
225(HR unit7)
229(HR unit8)
Defective temperature sensor connection
Defective temperature sensor
(Open/Short)
Defective outdoor unit PCB
Error No. Error Type Error Point Main Reasons
Abnormal value of sensor
measurement(Open / Short )
HR unit
Sub-cooling inlet pipe
temperature sensor
error
202(HR unit1)
206(HR unit2)
210(HR unit3)
214(HR unit4)
218(HR unit5)
222(HR unit6)
226(HR unit7)
230(HR unit8)
Defective temperature sensor connection
Defective temperature sensor
(Open/Short)
Defective outdoor unit PCB
Error No. Error Type Error Point Main Reasons
Abnormal value of sensor
measurement(Open / Short)
HR unit
Sub-cooling discharge
pipe temperature sensor
error
203(HR unit1)
207(HR unit2)
211(HR unit3)
215(HR unit4)
219(HR unit5)
223(HR unit6)
227(HR unit7)
231(HR unit8)
Error diagnosis and countermeasure flow chart
1) Check connection condition of temperature sensor and lead cable
2) Is value of temperature sensor normal? If not replace sensor
- Piping temperature sensor : 10°C = 10k : 25°C= 5k : 50°C= 1.8k
3) If connection of sensor and value is correct, replace outdoor unit PCB