Troubleshooting Guide
- 296 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. NOISE occurs
2. CNU defect
3. Temporary error of Timing mismatch
4. A/C product defect
Error
No.
Error Type Error Point Main Reasons
Received check sum is differ-
ent from calculated check
sum data
Central controller
Check sum Error
250
1. NOISE occurs
2. CNU defect
3. Temporary error of Timing mismatch
4. A/C product defect
Error
No.
Error Type Error Point Main Reasons
Length of received data : 0
Central controller
Receive Zero Error
251
1. NOISE occurs
2. CNU defect
3. Temporary error of Timing mismatch
4. A/C product defect
Error
No.
Error Type Error Point Main Reasons
Setting address and actual
address are different each
other
Central controller
Wrong Address Error
252
Error diagnosis and countermeasure flow chart
1) Check system setting address of central controller and actual address is matched or not
2) Re-start service program(engine) of central controller
3) Replace CNU