Air-to-Water Heat Pump _ 25
Part 1. Monobloc Unit
9. Performance Data
LWT : Leaving Water Temperature
TC: Total Capacity
PI: Power Input (kW)
Notice: Measuring procedure follows EN-14511
Notice: Above table values may not be matched according to installation condition
Model: AHBW126A0 [HM121M]
Model: AHBW146A0 [HM141M]
Model: AHBW166A0 [HM161M]
Outdoor
Temperature
LWT 7℃ LWT 10℃ LWT 13℃ LWT 15℃ LWT 18℃ LWT 20℃ LWT 22℃
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20℃ DB 10.59 2.44 11.92 2.62 13.26 2.81 14.40 2.98 15.60 3.16 16.70 3.34
30℃ DB 12.02 3.80 12.61 3.85 13.64 4.17 14.88 4.00 15.20 3.95 15.85 3.89
35℃ DB 11.07 4.10 12.08 4.23 13.00 4.31 14.08 4.34 14.50 4.00 14.98 4.27 15.57 4.43
40℃ DB 10.54 4.55 11.18 4.66 12.29 4.79 13.05 4.85 13.30 4.42 13.79 4.51 14.34 4.59
45℃ DB 8.89 4.88 9.87 4.96 10.86 5.05 11.76 5.13 12.75 5.21 13.16 5.15 13.57 5.08
Outdoor
Temperature
LWT 7℃ LWT 10℃ LWT 13℃ LWT 15℃ LWT 18℃ LWT 20℃ LWT 22℃
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20℃ DB 11.32 2.86 12.74 3.07 14.17 3.29 15.39 3.50 16.68 3.71 17.85 3.92
30℃ DB 12.85 4.45 13.48 4.52 14.58 4.88 15.91 4.69 16.25 4.63 16.95 4.56
35℃ DB 11.83 4.80 12.91 4.95 13.90 5.05 15.05 5.09 15.50 4.69 16.02 5.01 16.64 5.20
40℃ DB 11.27 5.34 11.95 5.46 13.14 5.61 13.95 5.69 14.21 5.18 14.75 5.28 15.32 5.39
45℃ DB 9.51 5.72 10.55 5.82 11.61 5.92 12.57 6.01 13.63 6.11 14.07 6.03 14.51 5.96
Outdoor
Temperature
LWT 7℃ LWT 10℃ LWT 13℃ LWT 15℃ LWT 18℃ LWT 20℃ LWT 22℃
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20℃ DB 11.76 3.09 13.24 3.32 14.72 3.56 15.99 3.78 17.32 4.01 18.54 4.23
30℃ DB 13.35 4.81 14.01 4.88 15.14 5.28 16.52 5.07 16.88 5.01 17.60 4.93
35℃ DB 12.29 5.19 13.41 5.36 14.44 5.46 15.63 5.51 16.10 5.07 16.64 5.42 17.28 5.62
40℃ DB 11.71 5.77 12.42 5.91 13.64 6.07 14.49 6.15 14.77 5.60 15.32 5.71 15.92 5.82
45℃ DB 9.87 6.19 10.96 6.29 12.06 6.40 13.06 6.50 14.15 6.61 14.61 6.52 15.07 6.44