EasyManua.ls Logo

LG HM031M - Page 33

LG HM031M
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30 _ Air-to-Water Heat Pump
Part 1. Monobloc Unit
9. Performance Data
LWT : Leaving Water Temperature
TC: Total Capacity
* : Total Capacity (Averaged value including defrost effect, kW)
PI: Power Input (kW)
Notice: Measuring procedure follows EN-14511
Notice: Above table values does not include humidification effect in the outdoor temperature below zero.
Model: AHBW168A0 [HM163M]
Outdoor
Temperature
LWT 30℃ LWT 35℃ LWT 40℃ LWT 45℃ LWT 50℃ LWT 55℃
TC PI TC PI TC PI TC PI TC PI TC PI
-20℃ DB 11.27 6.11 10.38 6.13 9.10 6.16 8.66 5.87
-15℃ DB 14.09 5.96 12.98 5.98 11.37 6.01 10.83 6.02 10.10 5.92
-7℃ DB 13.90 5.31 13.26 5.29 12.42 5.54 12.13 5.65 11.31 5.59 10.31 5.71
-2℃ DB 13.78 3.93 13.44 4.04 13.07 4.69 12.94 4.90 12.07 5.25 11.00 5.13
*2℃ DB 13.94 3.98 13.60 4.25 13.23 4.75 13.10 4.92 12.21 5.12 11.13 4.80
7℃ DB 16.40 3.71 16.00 3.81 15.56 4.42 15.41 4.62 14.37 4.95 13.09 4.84
10℃ DB 17.49 3.83 17.34 4.10 16.73 4.51 16.53 4.65 15.23 4.69 13.11 4.64
15℃ DB 18.05 3.19 17.61 3.18 16.95 3.66 16.68 4.07 15.45 4.62 12.36 4.13
18℃ DB 18.57 3.42 18.17 3.34 17.50 3.79 17.04 4.16 16.28 4.79 11.91 3.82

Related product manuals