Installation
34
Hydro Kit
Independent power module is required to protect a plate heat exchanger burst. When the outdoor
unit is operating, if Hydro Kit is suddenly powered off, a plate heat exchanger burst may happen
during oil-return and defrosting cycle in cooling mode.
How to install Independent Power Module
Step 1. Open the front panel of the control box
Independent Power Module
Step 2. Assemble the cover of independent power module, fix it tightly with bolts and connect wires.