System Set-Up
70
Hydro Kit
• DHW time setting
Determine following time duration : operation time of DHW tank heating, stop time of DHW tank
heating, and delay time of DHW tank heater operating.
- Active time : This time duration defines how long time DHW tank heating can be continued.
- Stop time : This time duration defines how long time DHW tank heating can be stopped. It is also
regarded as time gap between DHW tank heating cycle.
Th On Th Off
0 -0.5 ℃ 1.5 ℃
1 -1 ℃ 2 ℃
2 -2 ℃ 3 ℃
3 -3 ℃ 4 ℃
• TH on/off Variable, heating air
Setting Thermal on/off Air Temperature gap in heating mode
• TH on/off Variable, heating water
Setting Thermal on/off Water Temperature gap in heating mode
• TH on/off Variable, cooling air
Setting the step value to adjust air temperature gap in cooling mode
Th On Th Off
0 0.5 ℃ -0.5 ℃
1 1 ℃ -1 ℃
2 2 ℃ -2 ℃
3 3 ℃ -3 ℃
Th On Th Off
0 0.5 ℃ -0.5 ℃
1 1 ℃ -1 ℃
2 2 ℃ -2 ℃
3 3 ℃ -3 ℃
Th On Th Off
0 -2 ℃ 2 ℃
1 -3 ℃ 3 ℃
2 -4 ℃ 4 ℃
3 -1 ℃ 1 ℃
• TH on/off Variable, cooling water
Setting the step value to adjust water temperature gap in cooling mode