- 67 -
21
DC PEAK
(IPM Fault)
• Instant over current
• Over Rated current
• Poor insulation of IPM
• An instant over current in the U,V,W phase
- Comp lock
- The abnormal connection of U,V,W
• Over load condition
- Overcharging of refrigerant Pipe length.
Outdoor Fan is stop
• Poor insulation of compressor
Display
code
Title Cause of error Check point & Normal condition
Is installation
condition normal?
No
Yes
Yes
Recheck power and installation condition
1. Check Pipe clogging/distortion
2. Check Covering (Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
2. Check insulation resistance between compressor
terminal and pipe
Replace compressor if abnormality found
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
1. Check inverter PCB assembly 1 U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found
Is compressor
Wire connection
condition normal?
No
Yes
Check inverter PCB assembly 1 IPM normality
Replace inverter PCB assembly 1
Is inverter PCB assembly 1 normal?
No
n Error Diagnosis and Countermeasure Flow Chart
n Comp checking method
V
U
W
Comp
Copper
pipe
Comp
WARNING
Before checking PCB(Inverter) or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby
state of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other
parts.
Model Resistance(Ω) at 20°C
AHBW056A0
AHBW076A0
AHBW096A0
U-V 0.628(at 25˚C)
V-W 0.628(at 25˚C)
W-U 0.628(at 25˚C)
AHBW126A0
AHBW146A0
AHBW166A0
U-V 0.438(at 25˚C)
V-W 0.438(at 25˚C)
W-U 0.438(at 25˚C)
Model
Resistance(Ω) at 20°C
Terminal Inverter comp.
AHBW056A0
AHBW076A0
AHBW096A0
U-GND 2MΩ
V-GND 2MΩ
W-GND 2MΩ
AHBW126A0
AHBW146A0
AHBW166A0
U-GND 2MΩ
V-GND 2MΩ
W-GND 2MΩ